Skip to main content

News

Intrinsic Safety – Part 3 – Impact of Gas Group on loop approval and cable lengths.
transmitter-interface-system

Intrinsic Safety – Part 3 – Impact of Gas Group on loop approval and cable lengths.

Further to my previous articles: How to calculate an intrinsically safe loop approval (http://www.instrumentation.co.za/7571a) and Calculating intrinsically safe loop approvals – Part 2 (http://www.instrumentation.co.za/7782a), we consider the impact of Gas Group on cable lengths for IS loops.

In part 2, I discussed using Exic for zone 2 applications ‘Intrinsic Safety in normal operation’ i.e. with no safety factor required.

To repeat, firstly and importantly, there is a misconception that the Co values are defined by the design of barrier/isolator. The Co value is
actually defined in IEC/SANS60079-11: 2012 Table A.2 page 96 (102 of 149).

So, any barrier/isolator with 28V safety description will have Co = 83nF (Zone 0/1; IIC). In practice Co will define the maximum allowable cable length in most cases.

However as explained in part 2, using Exic where applicable is one method to have longer cable lengths.

Gas Group classification impacts Co parameter as per Figure 1.

impact of Gas Group on loop approval and cable lengths.
Figure 1 Co values

 

Intrinsic Safety
Figure 2 IIC IS loop for Zone 01 Co 83nF

Figure 2 shows an Exia loop with a Co=83nF. The max cable capacitance Cc=63nF. With a typical cable capacitance of 95nF/km, this
would equate to maximum cable of 660m.

If the loop was Exic, the Co=272nF, so Cc=252nF would theoretically allow 2.5kms of cable. i.e. no longer a limiting factor. (The limiting factor in this system is likely to be operating voltage at the end of the cable being high enough for the transmitter to work).

If the Gas Group were IIB, the Co=650nF which eliminates capacitance as a limiting factor.

Conclusions:

  1. For installations requiring long cable runs, classifying the area as zone 2 offers significant benefit.
  2. Alternatively, a IIB (or IIA) classification is another way of allowing longer cables lengths.

Comments or suggestions welcome.

Gary Friend PrEng
Sales Director

Extech Safety Systems (Pty) Ltd.
TEL : +27 (0) 11 791 6000
FAX : +27 (0) 11 792 8294
CELL : +27 (0) 83 309 8200
http://extech.co.za

Download the article

Sign up to our newsletter

Sign up to our newsletter today to learn more about hazardous area solutions that fit your needs. Our knowledgeable and skilled staff of specialists is ready to answer all of your questions.


Extech Safety Systems Published In SA Instrumentation & Control

  • Windows tablets for hazardous areas

    i.safe Mobile has expanded its intrinsically safe product range with the launch of the IS945.x series rugged Windows tablets, designed for use in hazardous and demanding industrial environments.

  • Hazardous area inspections

    The i.safe MOBILE IS940.1 tablet from Extech delivers the performance of a modern Android device, but in a package designed from the ground up for hazardous areas.

  • Unified endpoint management in hazardous industrial environments

    The strategic integration of SafeUEM‘s comprehensive end-point management platform with i.safe MOBILE‘s certified intrinsically safe devices delivers a unified solution specifically engineered to address the challenges of managing technology in hazardous industrial settings.

  • Windows tablets for Zone 1/21, Zone 2/22 and mining

    Extech is expanding its portfolio with the Windows-based tablets IS945.1, IS945.2, and IS945.M1. For the first time, EX certification is combined with full Windows compatibility, without compromising on software or security.

  • Hazardous area solutions

    Extech specialises in hazardous area solutions, with offerings ranging from intrinsically safe Zenier Barriers and galvanic isolators to networking infrastructure, mobile devices and RTLS.